1100 Volts Single Core Armoured Cables
(Aluminium Conductor) Type 'AYWY' to IS:1554(I) - 1988
Sl.     Normal Cross-Sectional Area of Conductor in mm2                          
No. Description Unit  1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000
  Constructional Details                                            
  Conductor (solid)                                          
1 Minimum number of wires nos. 1 1 1 1 1 6 6 6 6 12 15 15 15 30 30 30 53 53 53 53 91
2 Shape                   Circular   solid                           Circular Compacted               Circular 
              (noncom-
                                              pacted)
  Conductor (stranded)                                          
  Minimum number of wires nos. 3 3 3 3 7 6 6 6 6 12 15 15 15 30 30 30 53 53 53 53 91
  Shape       Circular  Stranded                   Circular Compacted               Circular 
              (noncom-
                                              pacted)
  Insulation      
3 Type                       PVC Compound Type A to IS:5831                    
4 Nominal thickness mm 1.1 1.2 1.3 1.3 1.3 1.3 1.5 1.5 1.7 1.7 1.9 1.9 2.1 2.3 2.5 2.7 3.0 3.4 3.9 3.9 3.9
  Armouring                                             
5 Type and Material     Single Layer of Round Hard Drawn Aluminium Wires  
6 Nominal Diameter of Wire   1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.6 1.6 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.5
7 Dia over laid up core     4.51 5.25 5.85 6.75 7.80 9.62 10.76 12.66 14.30 16.60 18.10 20.40 22.44 25.15 28.00 31.85 36.25 40.67 44.85 49.25
8 Dia over armoured (strip)     10.00 11.00 13.00 14.00 17.00 21.00 23.00 27.00 31.00 31.00 34.00 38.00 42.00 47.00 53.00 48.00 54.00 61.00 67.00 59.00
  Dia over armoured (wire)     7.31 8.05 8.65 9.55 10.60 12.42 13.56 15.46 17.10 19.80 21.30 23.60 25.64 28.35 31.20 35.85 40.25 44.67 48.85 54.25
  Outer sheath      
9 Type                       PVC Compound Type A to IS:5831                    
10 Colour     Black  
11 Minimum thickness mm 1.24 1.24 1.24 1.24 1.24 1.24 1.24 1.24 1.24 1.4 1.4 1.4 1.4 1.4 1.56 1.56 1.56 1.72 1.88 1.88 2.04
12 Approximate overall diameter of CBL mm   10.0 10.7 11.3 12.2 13.3 15.1 16.2 18.1 20.1 22.8 24.3 26.6 28.6 31.7 34.6 39.2 43.9 48.6 52.8 56.6
  ELECTRICAL CHARECTERSTICS      
13 Resistance of conductor per                                             
  1000m length of completed cable                                            
  a) Maximum d.c. resistance                        
      at 20 Deg. C. ohm 18.1 12.1 7.41 4.61 3.08 1.91 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.1 0.0778 0.0605 0.0469 0.0367 0.0291
  b) a.c. resistance at 70 Deg. C ohm 21.72 14.52 8.89 5.53 3.70 2.29 1.44 1.042 0.77 0.532 0.39 0.304 0.248 0.198 0.152 0.122 0.0962 0.0762 0.0608 0.0498 0.0421
         
14 Continuous current rating (a.c.) of                                             
  cables under standard conditions      
  (a) For two single core cables      
  touching in horizontal formation-                                            
  i) When laid direct in ground amps 21 28 36 44 59 75 97 120 145 170 205 230 265 300 335 370 410 435 485 530 580
  ii) When laid in ducts amps 19 25 33 42 56 71 93 110 130 155 180 200 220 240 270 295 335 355 395 440 490
  iii)When laid in air amps 18 25 32 41 56 72 99 120 150 185 215 240 270 305 350 395 455 490 560 640 740
  (b) For three single core cables                                            
  touching in trefoil formation                                            
  i) When laid direct in ground amps 17 24 31 39 51 66 86 100 120 140 175 195 220 240 270 295 325 345 390 440 490
  ii) When laid in ducts amps 17 24 30 37 51 65 84 100 115 135 155 170 190 210 225 245 275 295 320 345 370
  iii)When laid in air amps 15 21 27 35 47 64 84 105 130 155 190 220 250 290 335 380 435 480 550 640 720
15 Reactance per 1000m length of                                            
  cable at 50 Hz(assuming 3 single ohm 0.19 0.18 0.16 0.15 0.14 0.13 0.11 0.105 0.1 0.095 0.09 0.08 0.82 0.079 0.075 0.072 0.070 0.069 0.067 0.065 0.06
  core cables laid in trefoil touching                          
  formation)                                            
16 Capacitance per 1000m length of micro                                          
  cable (assuming 3 single core CBL farad 0.35 0.39 0.44 0.51 0.61 0.76 0.82 0.93 0.95 1.11 1.2 1.3 1.3 1.33 1.4 1.43 1.5 1.5 1.5 1.7 1.92
  laid in trefoil touching formation                                            
17 Minimum volume resistivity                                            
  of PVC insulation cm                     1 x 10 13 at 27 Deg C and 1 x 10 10 at 70 Deg C                    
18 Maximum permissible shortcircuit kilo                                           
  current for duration of one sencond amps 0.114 0.190 0.304 0.456 0.760 1.216 1.900 2.660 3.800 5.320 7.220 9.120 11.400 14.060 18.240 22.800 30.400 38.000 47.880 60.800 76.000
19 Voltage drop per 1000m length of                                             
  cable (assuming 3 single core       
  cables used on 3 phase a.c system)                                            
  a) When laid direct in ground volts 639 604 478 374 327 262 215 180 163 132 118 104 99 87 80 71 62 61 54 54 50
b) When laid in ducts volts 639 604 462 355 327 258 210 180 156 126 104 92 85 76 66 59 54 52 45 42 38
c)When laid in air volts 565 528 416 336 301 255 210 191 175 146 132 121 113 106 99 92 90 83 87 88 87
  GENERAL  :    
20 Approximate net weight per 1000 m  kg 120 140 160 180 200 250 320 370 450 500 730 840 970 1160 1455 1700 2210 2730 3435 4220 5180
  length of finished cable                                            
21 Stranded length of cable (subject to  m                 500                        
  a manufacturing tolerance +/-5%)                                            
22 Drum Dimensions-    
  a) Approximate overall height  mm 740 840 840 840 840 840 940 940 1040 1140 1140 1250 1250 1450 1450 1550 1650 1850 2050 2265 2365
  b) Approximate outer width mm 515 515 515 515 665 665 690 690 715 715 855 855 855 855 855 910 1130 1180 1180 1420 1550
23 Approximate gross weight of drum kg 105 120 130 140 155 180 230 255 310 380 465 550 615 760 905 1090 1415 1815 2295 2960 3540
24 Minimum bending radius for laying                    15 x Overall Diameter of cable                
  of cable                                             
25 Recommended pulling force:    
  a) When conductor pulled by pulling                                             
  eye N                 30 x Total Conductor Area in mm2                        
  b) When cable pulled with stocking  N 5 x D2 where D is the Overall Diameter of cable in mm2  
            STRANDED CONDUCTOR IS ALSO PERMISSIBLE IN THESE SIZES