1100
Volts Four Core Armoured Cables |
|
(Aluminium
Conductor) Type 'AYWY' & 'AYFY' to
IS:1554(I) - 1988 |
|
Sl. |
|
|
Normal Cross-Sectional
Area of Conductor in mm2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
No. |
Description |
Unit |
1.5 |
2.5 |
4 |
6 |
10 |
16 |
25 |
35 |
50 |
70 |
95 |
120 |
150 |
185 |
240 |
300 |
400 |
500 |
630 |
|
|
Constructional
Details |
|
|
|
|
|
Conductor (Solid) |
|
|
|
|
1 |
Minimum number of
wires |
nos. |
1 |
1 |
1 |
1 |
1 |
6 |
6 |
6 |
6 |
12 |
15 |
15 |
15 |
30 |
30 |
30 |
53 |
53 |
53 |
|
2 |
Shape |
|
|
|
Circular solid |
|
|
compaced |
|
|
|
|
|
|
Shaped |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Conductor (Stranded) |
|
|
|
|
|
Minimum number of
wires |
nos. |
3 |
3 |
3 |
3 |
7 |
6 |
6 |
6 |
6 |
12 |
15 |
15 |
15 |
30 |
30 |
30 |
53 |
53 |
53 |
|
|
Shape |
|
|
|
Circular stranded |
|
|
compaced |
|
|
|
|
|
|
Shaped |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Insulation |
|
|
|
|
|
|
|
3 |
Type |
|
|
|
|
|
|
|
|
|
|
|
PVC Compound Type A to IS:5831 |
|
|
|
|
|
|
|
|
|
4 |
Nominal thickness |
mm |
0.8 |
0.9 |
1.0 |
1.0 |
1.0 |
1.0 |
1.2 |
1.2 |
1.4 |
1.4 |
1.6 |
1.6 |
1.8 |
2.0 |
2.2 |
2.4 |
2.6 |
3.0 |
3.4 |
|
5 |
Dia over laidup core |
mm |
|
|
11.48 |
13.20 |
14.14 |
15.10 |
17.91 |
20.87 |
24.70 |
27.99 |
32.39 |
35.46 |
39.64 |
43.98 |
49.68 |
55.22 |
62.92 |
|
|
|
6 |
Colour Scheme for
identification |
|
|
|
|
|
|
|
|
|
|
|
Red, Yellow, Blue, Black |
|
|
|
|
|
|
|
|
|
7 |
Dia over inner sheath |
mm |
|
|
12.48 |
14.20 |
15.14 |
16.10 |
18.91 |
21.87 |
25.90 |
29.19 |
33.59 |
36.86 |
41.04 |
45.58 |
51.28 |
57.22 |
64.92 |
|
|
|
8 |
Dia over armoured (Strip) |
mm |
|
|
|
|
16.74 |
17.70 |
20.51 |
23.47 |
27.50 |
30.79 |
35.19 |
38.46 |
42.64 |
47.18 |
52.88 |
58.82 |
66.52 |
|
|
|
|
Dia over armoured (Wire) |
mm |
|
|
15.28 |
17.00 |
18.34 |
19.30 |
22.11 |
25.07 |
29.90 |
33.19 |
37.59 |
40.86 |
46.04 |
50.58 |
56.28 |
63.52 |
71.22 |
|
|
|
|
Inner Sheath |
|
|
|
|
|
|
|
9 |
Type |
|
|
|
Extruded |
|
|
|
|
|
|
|
|
|
Extruded |
|
|
|
|
|
|
|
10 |
Material |
|
|
|
PVC |
|
|
|
|
|
|
|
|
|
PVC Taps |
|
|
|
|
|
|
|
11 |
Minimum Thickness |
|
0.3 |
0.3 |
0.3 |
0.3 |
0.3 |
0.3 |
0.3 |
0.3 |
0.4 |
0.4 |
0.5 |
0.5 |
0.5 |
0.6 |
0.6 |
0.7 |
0.7 |
0.7 |
0.7 |
|
|
Armouring |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
12 |
Type & Material |
|
|
Steel Round Wire |
|
|
|
Single Layer of Flat |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Galvanised Steel Strips |
|
|
|
|
|
|
|
13 |
Dia over armoured (Strip) |
|
|
|
|
|
16.74 |
17.70 |
20.51 |
23.47 |
27.50 |
30.79 |
35.19 |
38.46 |
42.64 |
47.18 |
52.88 |
58.82 |
66.52 |
|
|
|
|
Dia over armoured (Wire) |
|
|
|
15.28 |
17.0 |
18.3 |
19.30 |
22.11 |
25.07 |
29.90 |
33.19 |
37.59 |
40.86 |
46.04 |
50.58 |
56.28 |
63.52 |
71.22 |
|
|
|
14 |
Nominal diameter of
wires/thickness of strip |
mm |
1.4 |
1.4 |
1.4 |
1.4 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
|
|
Outer Sheath |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
15 |
Type |
|
|
|
|
|
|
|
|
|
|
|
PVC Compound Type ST 1 to IS:5831 |
|
|
|
|
|
|
|
|
|
16 |
Colour |
|
|
|
Black |
|
|
|
|
17 |
Minimum Thickness |
mm |
1.24 |
1.24 |
1.24 |
1.24 |
1.40 |
1.40 |
1.40 |
1.40 |
1.56 |
1.56 |
1.72 |
1.88 |
1.88 |
2.04 |
2.36 |
2.52 |
2.84 |
3.00 |
3.00 |
|
18 |
Approximate overall
diameter of cable (Strip) |
mm |
|
|
|
|
19.74 |
20.70 |
23.51 |
26.47 |
30.82 |
34.11 |
38.89 |
42.46 |
46.64 |
51.78 |
57.88 |
64.06 |
72.52 |
|
|
|
|
Approximate overall
diameter of cable (Wire) |
mm |
|
|
17.96 |
19.68 |
21.34 |
22.40 |
25.11 |
28.39 |
33.22 |
36.51 |
41.33 |
44.96 |
50.44 |
55.28 |
61.28 |
69.22 |
77.22 |
|
|
|
|
ELECTRICAL
CHARACTERISTICS |
|
|
|
|
|
19 |
Resistance
of conductor per |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1000m length of completed cable |
|
|
|
|
|
|
|
a) Maximum d.c.
resistance at 20 Deg C |
ohm |
18.1 |
12.1 |
7.41 |
4.61 |
3.08 |
1.91 |
1.20 |
0.868 |
0.641 |
0.443 |
0.320 |
0.253 |
0.206 |
0.164 |
0.125 |
0.1 |
0.0778 |
0.0605 |
0.0469 |
|
|
b) a.c. resistance at 70 Deg. C |
ohm |
21.72 |
14.52 |
8.89 |
5.53 |
3.70 |
2.29 |
1.44 |
1.042 |
0.77 |
0.532 |
0.385 |
0.304 |
0.248 |
0.198 |
0.152 |
0.122 |
0.0962 |
0.0762 |
0.0608 |
|
20 |
Continuous current rating (a.c.)
of |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
cables under standard conditions |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
i) When laid direct
in ground |
amps |
16 |
21 |
28 |
35 |
46 |
60 |
76 |
92 |
110 |
135 |
165 |
185 |
210 |
235 |
275 |
305 |
335 |
360 |
400 |
|
|
ii) When laid in
ducts |
amps |
14 |
18 |
23 |
30 |
39 |
50 |
63 |
77 |
95 |
115 |
140 |
155 |
175 |
200 |
235 |
260 |
290 |
305 |
340 |
|
|
iii)When laid in air |
amps |
13 |
18 |
23 |
30 |
40 |
51 |
70 |
86 |
105 |
130 |
155 |
180 |
205 |
240 |
280 |
315 |
375 |
410 |
470 |
|
21 |
Reactance per 1000m
length of cable |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
at 50 Hz |
ohm |
0.092 |
0.087 |
0.081 |
0.073 |
0.064 |
0.055 |
0.054 |
0.05 |
0.05 |
0.046 |
0.043 |
0.042 |
0.042 |
0.042 |
0.041 |
0.040 |
0.040 |
0.040 |
0.040 |
|
22 |
Capacitance between conductors
per |
Micro |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1000m length of cable |
farad |
0.372 |
0.408 |
0.45 |
0.51 |
0.62 |
0.76 |
0.80 |
0.90 |
0.90 |
1.03 |
1.050 |
1.16 |
1.16 |
1.16 |
1.22 |
1.24 |
1.30 |
1.30 |
1.30 |
|
|
23 |
Minimum volume
resistivity of PVC Insu |
Ohmcm |
|
|
|
|
|
|
|
|
|
|
1 X 10 13 AT 27 Deg C and 1 x 10 10 at 70 Deg C |
|
|
|
|
|
|
|
|
|
24 |
Maximum permissible
shortcircuit |
kilo |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
current for duration of one second |
amps |
0.114 |
0.190 |
0.304 |
0.456 |
0.760 |
1.216 |
1.900 |
2.660 |
3.800 |
5.320 |
7.220 |
9.120 |
11.400 |
14.060 |
18.240 |
22.800 |
30.400 |
38.000 |
47.880 |
|
25 |
Voltage drop
per 1000m length of cable |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(assuming cables used on single phase a.c. |
|
|
|
|
|
|
systems) |
|
|
|
|
|
|
a) When laid direct in ground |
volts |
602 |
528 |
431 |
335 |
295 |
238 |
190 |
166 |
147 |
125 |
112 |
99 |
91 |
81 |
76 |
69 |
60 |
54 |
51 |
|
|
b) When laid in ducts |
volts |
527 |
453 |
354 |
287 |
250 |
198 |
157 |
139 |
127 |
106 |
95 |
83 |
76 |
69 |
65 |
59 |
52 |
45 |
43 |
|
|
c) When laid in air |
volts |
489 |
453 |
354 |
287 |
256 |
202 |
175 |
155 |
140 |
120 |
105 |
97 |
89 |
81 |
78 |
71 |
68 |
61 |
59 |
|
|
GENERAL : |
|
|
|
|
26 |
Approximate net weight per |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1000m length of finished cable (Strip) |
kg |
|
|
|
|
672 |
756 |
993 |
1206 |
1565 |
1927 |
2476 |
2930 |
3477 |
4216 |
5237 |
6361 |
7926 |
|
|
|
|
Approximate net weight per |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1000m length of finished cable (Wire) |
kg |
|
|
614 |
728 |
890 |
981 |
1244 |
1512 |
2104 |
2528 |
3168 |
3264 |
4248 |
5025 |
6090 |
7996 |
9648 |
|
|
|
27 |
Standard length of
cable (Subject to a |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
manufacturing tolerance +/-5%) |
m |
|
|
|
|
|
|
|
|
500 |
|
|
|
|
|
|
|
|
250 |
|
|
28 |
Drum Dimensions- |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
a) Approximate
overall height |
mm |
940 |
940 |
1040 |
1140 |
1140 |
1250 |
1250 |
1250 |
1450 |
1650 |
1650 |
1850 |
2050 |
2265 |
2365 |
2050 |
2050 |
2265 |
2465 |
|
|
b) Approximate outer
width |
mm |
690 |
690 |
715 |
715 |
715 |
855 |
855 |
855 |
855 |
1130 |
1130 |
1180 |
1180 |
1420 |
1550 |
1240 |
1240 |
1350 |
1450 |
|
29 |
Approximate gross
weight of drum |
kg |
310 |
355 |
430 |
470 |
495 |
560 |
675 |
775 |
990 |
1325 |
1600 |
2000 |
2390 |
3050 |
3715 |
2285 |
2720 |
3420 |
4195 |
|
30 |
Minimum bending
radius for laying of CBL |
|
|
|
|
|
|
|
|
|
|
|
12
x Overall Diameter of
Cable |
|
|
|
|
|
|
|
|
|
31 |
Recommended pulling
force: |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
a) When conductor
pulled by pulling eye |
N |
|
|
|
|
|
|
|
|
|
|
30 x Total Conductor Area in mm2 |
|
|
|
|
|
|
|
|
|
|
b) When cable pulled with stocking |
N |
|
|
|
|
|
|
|
|
|
|
9 x D2 where D is
the Overall Diameter of cable in mm |
|
|
|
|
|
|
|
|
|
|
|
|
STRANDED CONDUCTOR IS ALSO PERMISSIBLE IN THESE SIZES |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|