1100 Volts Armoured
Control Cables - 1.5 mm2 |
|
Type
'YWY' & 'YFY' to IS:1554(I) - 1988 |
|
Sl. |
|
|
NUMBER OF CORES |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
No. |
Description |
Unit |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
10 |
12 |
14 |
16 |
19 |
21 |
24 |
27 |
30 |
33 |
37 |
44 |
52 |
61 |
|
Constructional
Details |
|
|
|
|
|
|
Conductor |
|
|
|
|
|
1 |
Material |
|
|
|
|
|
|
|
|
|
|
|
PLANNED ANNEALED COPPER |
|
|
|
|
|
|
|
|
|
2 |
Number of wires |
nos. |
|
|
|
|
|
|
|
|
|
|
ONE |
|
|
|
|
|
|
|
|
|
3 |
Shape |
|
|
|
|
|
|
|
|
|
|
|
SOLID CIRCULAR |
|
|
|
|
|
|
|
|
|
Insulation |
|
|
|
|
|
|
|
4 |
Type |
|
|
|
|
|
|
|
|
|
|
|
PVC Compound Type A to IS:5831 |
|
|
|
|
|
|
|
|
|
5 |
Nominal thickness |
mm |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
6 |
Colour Scheme for
identification |
|
TWO CORE - Red Black |
|
|
|
|
|
|
THREE CORE - Red, Yellow,
Blue |
|
|
|
|
|
|
|
|
FOUR CORE - Red, Yellow,
Blue, Black |
|
FOUR CORE - Red, Yellow,
Blue, Black, Grey |
|
|
|
|
|
|
|
SIX CORE AND ABOVE - |
Two adjacent cores (I.e
counting core & direction core) in each layer |
|
|
|
|
|
|
|
|
|
|
|
shall be Blue &
Yellow respectively and remaining cores shall be Grey |
|
|
|
|
|
|
|
7 |
Dia over laid up core |
|
6.60 |
7.10 |
8.00 |
8.90 |
9.90 |
9.90 |
10.70 |
11.40 |
12.00 |
13.20 |
14.50 |
15.50 |
16.50 |
17.50 |
19.70 |
20.20 |
21.10 |
22.00 |
23.00 |
26.30 |
27.70 |
29.60 |
8 |
Dia over inner sheath |
|
7.60 |
8.10 |
9.00 |
9.90 |
10.90 |
10.90 |
11.70 |
12.40 |
13.00 |
14.20 |
15.50 |
16.50 |
17.50 |
18.50 |
20.70 |
21.20 |
22.50 |
23.40 |
24.40 |
27.70 |
29.20 |
31.10 |
9 |
Dia over Armoured |
|
10.40 |
10.90 |
11.80 |
12.70 |
13.70 |
13.70 |
14.50 |
15.20 |
15.80 |
16.00 |
17.30 |
18.30 |
19.30 |
20.30 |
22.50 |
23.00 |
24.30 |
25.20 |
26.20 |
29.50 |
31.00 |
32.90 |
|
Inner Sheath |
|
|
|
|
|
|
|
|
10 |
Type |
|
|
|
|
Extruded |
|
|
|
|
|
|
|
|
Extruded |
|
|
|
|
|
|
|
|
11 |
Material |
|
|
|
|
PVC |
|
|
|
|
|
|
|
|
PVC Taps |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
12 |
Minimum Thickness |
|
0.30 |
0.30 |
0.30 |
0.30 |
0.30 |
0.30 |
0.30 |
0.30 |
0.30 |
0.30 |
0.30 |
0.30 |
0.30 |
0.30 |
0.30 |
0.30 |
0.30 |
0.30 |
0.30 |
0.30 |
0.40 |
0.40 |
|
Armouring |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
13 |
Type & Material |
|
|
|
|
Single Layer of Round |
|
|
|
|
|
|
|
|
Single Layer of Flat |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Galvanised Steel wires |
|
|
|
|
|
|
|
|
Galvanised Steel Strips |
|
|
|
|
|
|
|
|
14 |
Nominal diameter of
wires/thickness of strip |
mm |
1.40 |
1.40 |
1.40 |
1.40 |
1.40 |
1.40 |
1.40 |
1.40 |
1.40 |
0.80 |
0.80 |
0.80 |
0.80 |
0.80 |
0.80 |
0.80 |
0.80 |
0.80 |
0.80 |
0.80 |
0.80 |
0.80 |
|
Outer Sheath |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
15 |
Type |
|
|
|
|
|
|
|
|
|
|
|
PVC Compound Type ST 1 to IS:5831 |
|
|
|
|
|
|
|
|
|
|
16 |
Colour |
|
|
|
Black |
|
|
|
|
|
17 |
Minimum Thickness |
mm |
1.24 |
1.24 |
1.24 |
1.24 |
1.24 |
1.24 |
1.40 |
1.40 |
1.40 |
1.40 |
1.40 |
1.40 |
1.40 |
1.40 |
1.40 |
1.40 |
1.40 |
1.40 |
1.40 |
1.56 |
1.56 |
1.56 |
|
Approximate overall
diameter of cable |
mm |
13.10 |
13.60 |
14.50 |
15.40 |
16.40 |
16.40 |
17.20 |
17.90 |
18.80 |
19.00 |
20.30 |
21.30 |
22.30 |
23.30 |
25.50 |
26.00 |
27.30 |
28.20 |
29.20 |
32.80 |
34.30 |
36.20 |
|
ELECTRICAL
CHARACTERISTICS |
|
|
|
|
|
|
19 |
Resistance
of conductor per |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1000m length of completed cable |
|
|
|
|
|
|
|
a) Maximum d.c.
resistance at 20 Deg C |
ohm |
|
|
|
|
|
|
|
|
|
12.1 |
|
|
|
|
|
|
|
|
|
|
|
b) a.c. resistance at 70 Deg. C |
ohm |
|
|
|
|
|
|
|
|
|
14.48 |
|
|
|
|
|
|
|
|
|
|
20 |
Continuous current rating (a.c.)
of |
|
|
|
|
|
|
|
cables under standard conditions |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
i) When laid direct
in ground |
amps |
23 |
21 |
21 |
16 |
15 |
14 |
14 |
13 |
13 |
12 |
11 |
11 |
10 |
10 |
9 |
9 |
9 |
8 |
8 |
7 |
7 |
6 |
|
ii) When laid in
ducts |
amps |
20 |
17 |
17 |
14 |
13 |
13 |
12 |
12 |
11 |
10 |
10 |
9 |
9 |
8 |
8 |
8 |
7 |
7 |
7 |
6 |
6 |
6 |
|
iii)When laid in air |
amps |
20 |
17 |
17 |
14 |
13 |
13 |
12 |
12 |
11 |
10 |
10 |
9 |
9 |
8 |
8 |
8 |
7 |
7 |
7 |
6 |
6 |
6 |
21 |
Reactance per 1000m
length of cable |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
at 50 Hz |
ohm |
0.092 |
0.092 |
0.092 |
0.09 |
0.092 |
0.092 |
0.092 |
0.092 |
0.092 |
0.092 |
0.092 |
0.092 |
0.092 |
0.092 |
0.092 |
0.092 |
0.092 |
0.092 |
0.092 |
0.092 |
0.092 |
0.092 |
22 |
Capacitance between conductors
per |
Micro |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1000m length of cable |
farad |
0.113 |
0.113 |
0.113 |
0.113 |
0.113 |
0.113 |
0.113 |
0.113 |
0.113 |
0.113 |
0.113 |
0.113 |
0.113 |
0.113 |
0.113 |
0.113 |
0.113 |
0.113 |
0.113 |
0.113 |
0.113 |
0.113 |
23 |
Minimum volume
resistivity of PVC Insu |
Ohmcm |
|
|
|
|
|
|
|
|
|
|
1 X 10 13 AT 27 Deg C and 1 x 10 10 at 70 Deg C |
|
|
|
|
|
|
|
|
|
24 |
Maximum permissible
shortcircuit |
kilo |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
current for duration of one second |
amps |
0.172 |
0.172 |
0.172 |
0.17 |
0.172 |
0.172 |
0.172 |
0.172 |
0.172 |
0.172 |
0.172 |
0.172 |
0.172 |
0.172 |
0.172 |
0.172 |
0.172 |
0.172 |
0.172 |
0.172 |
0.172 |
0.172 |
25 |
Voltage drop
per 1000m length of cable |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(assuming cables used on single phase a.c. |
|
|
|
|
|
|
|
systems) |
|
|
|
|
|
|
|
a) When laid direct in ground |
volts |
666 |
608 |
608 |
463 |
434 |
405 |
|
|
376 |
348 |
318 |
318 |
290 |
|
261 |
261 |
261 |
|
232 |
203 |
203 |
174 |
|
b) When laid in ducts |
volts |
580 |
492 |
492 |
405 |
376 |
376 |
|
|
318 |
290 |
290 |
261 |
261 |
|
232 |
232 |
203 |
|
203 |
174 |
174 |
174 |
|
c) When laid in air |
volts |
580 |
492 |
492 |
405 |
376 |
376 |
|
|
318 |
290 |
290 |
261 |
261 |
|
232 |
232 |
203 |
|
203 |
174 |
174 |
174 |
|
GENERAL : |
|
|
|
|
|
|
26 |
Approximate net weight per |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1000m length of finished cable |
kg |
351 |
394 |
449 |
506 |
565 |
586 |
640 |
687 |
748 |
726 |
813 |
889 |
989 |
1069 |
1205 |
1291 |
1420 |
1521 |
1646 |
1937 |
2180 |
2454 |
27 |
Standard length of
cable (Subject to a |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
manufacturing tolerance +/-5%) |
m |
|
|
|
|
|
|
|
|
500 |
|
|
|
|
|
|
|
|
|
|
|
28 |
Drum Dimensions- |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
a) Approximate
overall height |
mm |
840 |
940 |
940 |
940 |
940 |
940 |
|
|
1140 |
1140 |
1140 |
1140 |
1140 |
|
1250 |
1250 |
1250 |
1450 |
1450 |
1450 |
1550 |
1650 |
|
b) Approximate outer
width |
mm |
665 |
690 |
690 |
690 |
690 |
690 |
|
|
715 |
715 |
715 |
715 |
715 |
|
855 |
855 |
855 |
855 |
855 |
855 |
910 |
1130 |
29 |
Approximate gross
weight of drum |
kg |
275 |
310 |
330 |
360 |
400 |
405 |
|
|
545 |
435 |
485 |
530 |
575 |
|
705 |
740 |
795 |
845 |
945 |
1090 |
1270 |
1465 |
30 |
Minimum bending
radius for laying of CBL |
|
|
|
|
|
|
|
|
|
|
|
12
x Overall Diameter of
Cable |
|
|
|
|
|
|
|
|
|
31 |
Recommended pulling
force: |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
a) When conductor
pulled by pulling eye |
N |
|
|
|
|
|
|
|
|
|
|
50 x Total Conductor Area in mm2 |
|
|
|
|
|
|
|
|
|
|
b) When cable pulled with stocking |
N |
|
|
|
|
|
|
|
|
|
|
9 x D2 where D is
the Overall Diameter of cable in mm |
|
|
|
|
|
|
|
|
|
|
|
|
STRANDED CONDUCTOR IS ALSO PERMISSIBLE IN THESE SIZES |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|