| 1100 Volts Twin Core Unarmoured Cables | |||||||||||||||||||
| (Aluminium Conductor) Type 'AYY' to IS:1554(I) - 1988 | |||||||||||||||||||
| Sl. | Normal Cross-Sectional Area of Conductor in mm2 | ||||||||||||||||||
| No. | Description | Unit | 1.5 | 2.5 | 4 | 6 | 10 | 16 | 25 | 35 | 50 | 70 | 95 | 120 | 150 | 185 | 240 | 300 | 400 |
| Constructional Details | |||||||||||||||||||
| Conductor (solid) | |||||||||||||||||||
| 1 | Minimum number of wires | nos. | 1 | 1 | 1 | 1 | 1 | 6 | 6 | 6 | 6 | 12 | 15 | 15 | 15 | 30 | 30 | 30 | 53 |
| 2 | Shape | Circular Solid | Compacted | shaped | |||||||||||||||
| Conductor (stranded) | |||||||||||||||||||
| Minimum number of wires | nos. | 3 | 3 | 3 | 3 | 7 | 6 | 6 | 6 | 6 | 12 | 15 | 15 | 15 | 30 | 30 | 30 | 53 | |
| Shape | Circular Stranded | Compacted | shaped | ||||||||||||||||
| Insulation | |||||||||||||||||||
| 3 | Type | PVC Compound Type A to IS:5831 | |||||||||||||||||
| 4 | Nominal thickness | mm | 0.8 | 0.9 | 1.0 | 1.0 | 1.0 | 1.0 | 1.2 | 1.2 | 1.4 | 1.4 | 1.6 | 1.6 | 1.8 | 2 | 2.2 | 2.4 | 2.6 |
| 5 | Colour scheme for identification Inner & Outer | Red & Black | |||||||||||||||||
| sheath (Applied in one operation) | |||||||||||||||||||
| Dia over laid up core | 9.45 | 10.87 | 11.64 | 11.03 | 13.55 | 15.03 | 17.78 | 19.91 | 23.18 | 25.13 | 28.40 | 31.33 | 35.14 | 39.12 | 44.15 | ||||
| Dia over inner sheath | 10.45 | 11.87 | 12.62 | 12.03 | 14.55 | 16.03 | 18.78 | 21.11 | 24.38 | 26.53 | 29.80 | 32.73 | 36.54 | 41.12 | 46.15 | ||||
| 6 | Type | PVC Compound TypeST1 to IS:5831 | |||||||||||||||||
| 7 | Colour | Black | |||||||||||||||||
| 8 | Minimum thickness of inner sheath | 0.30 | 0.30 | 0.30 | 0.30 | 0.30 | 0.30 | 0.30 | 0.30 | 0.30 | 0.30 | 0.40 | 0.40 | 0.40 | 0.50 | 0.50 | 0.60 | 0.70 | |
| 9 | Nominal thickness of outer sheath | 1.80 | 1.80 | 1.80 | 1.80 | 1.80 | 1.80 | 2.00 | 2.00 | 2.00 | 2.00 | 2.00 | 2.00 | 2.40 | 2.40 | 2.60 | 2.80 | 3.20 | |
| 10 | Approximate overall diameter of CBL | mm | 14.15 | 15.57 | 16.34 | 15.63 | 18.15 | 29.63 | 22.38 | 24.71 | 27.98 | 30.53 | 33.80 | 36.73 | 40.54 | 45.12 | 50.55 | ||
| ELECTRICAL CHARECTERSTICS | |||||||||||||||||||
| 11 | Resistance of conductor per | ||||||||||||||||||
| 1000m length of completed cable | |||||||||||||||||||
| a) Maximum d.c. resistance | |||||||||||||||||||
| at 20 Deg. C. | ohm | 18.1 | 12.1 | 7.41 | 4.61 | 3.08 | 1.91 | 1.20 | 0.868 | 0.641 | 0.443 | 0.320 | 0.253 | 0.206 | 0.164 | 0.125 | 0.1 | 0.0778 | |
| b) a.c. resistance at 70 Deg. C | ohm | 21.72 | 14.52 | 8.89 | 5.53 | 3.70 | 2.29 | 1.44 | 1.042 | 0.77 | 0.532 | 0.385 | 0.304 | 0.248 | 0.198 | 0.152 | 0.122 | 0.0962 | |
| 12 | Continuous current rating (a.c.) of | ||||||||||||||||||
| cables under standard conditions | |||||||||||||||||||
| i) When laid direct in ground | amps | 18 | 25 | 32 | 40 | 55 | 70 | 90 | 110 | 135 | 160 | 190 | 210 | 240 | 275 | 320 | 355 | 385 | |
| ii) When laid in ducts | amps | 16 | 21 | 27 | 34 | 45 | 58 | 76 | 92 | 115 | 140 | 170 | 190 | 210 | 240 | 275 | 305 | 345 | |
| iii)When laid in air | amps | 16 | 21 | 27 | 35 | 47 | 58 | 78 | 99 | 125 | 150 | 185 | 210 | 240 | 275 | 325 | 365 | 420 | |
| 13 | Reactance per 1000m length of | ||||||||||||||||||
| cable at 50 Hz | ohm | 0.092 | 0.087 | 0.081 | 0.073 | 0.064 | 0.055 | 0.054 | 0.05 | 0.05 | 0.046 | 0.043 | 0.042 | 0.042 | 0.042 | 0.041 | 0.040 | 0.040 | |
| 14 | Capacitance between conductors per 1000m | micro | |||||||||||||||||
| length of cable | farad | 0.113 | 0.12 | 0.13 | 0.14 | 0.16 | 0.18 | 0.18 | 0.2 | 0.2 | 0.21 | 0.22 | 0.23 | 0.23 | 0.23 | 0.23 | 0.23 | 0.24 | |
| 15 | Minimum volume resistivity | ||||||||||||||||||
| of PVC insulation | cm | 1 x 10 13 at 27 Deg C and 1 x 10 10 at 70 Deg C | |||||||||||||||||
| 16 | Maximum permissible shortcircuit | kilo | |||||||||||||||||
| current for duration of one sencond | amps | 0.114 | 0.190 | 0.304 | 0.456 | 0.760 | 1.216 | 1.900 | 2.660 | 3.800 | 5.320 | 7.220 | 9.120 | 11.400 | 14.060 | 18.240 | 22.800 | 30.400 | |
| 17 | Voltage drop per 1000m length of | ||||||||||||||||||
| cable (assuming cable used on single phase | |||||||||||||||||||
| a.c system) | |||||||||||||||||||
| a) When laid direct in ground | volts | 782 | 726 | 570 | 442 | 408 | 320 | 260 | 228 | 208 | 170 | 148 | 128 | 120 | 112 | 100 | 92 | 80 | |
| b) When laid in ducts | volts | 696 | 610 | 480 | 376 | 334 | 266 | 218 | 192 | 178 | 150 | 132 | 116 | 106 | 98 | 86 | 78 | 72 | |
| c)When laid in air | volts | 696 | 610 | 480 | 388 | 348 | 270 | 224 | 206 | 192 | 162 | 144 | 128 | 120 | 112 | 102 | 94 | 88 | |
| GENERAL : | |||||||||||||||||||
| 18 | Approximate net weight per 1000 m | kg | 140 | 175 | 234 | 268 | 325 | 322 | 435 | 519 | 661 | 788 | 1021 | 1244 | 1497 | 1900 | 2247 | 2786 | 3497 |
| length of finished cable | |||||||||||||||||||
| 19 | Stranded length of cable (subject to | m | 500 | 250 | 250 | ||||||||||||||
| a manufacturing tolerance +/-5%) | |||||||||||||||||||
| 20 | Drum Dimensions- | ||||||||||||||||||
| a) Approximate overall height | mm | 840 | 840 | 840 | 840 | 940 | 1040 | 1040 | 1140 | 1250 | 1250 | 1450 | 1450 | 1550 | 1650 | 1650 | 1550 | 1650 | |
| b) Approximate outer width | mm | 515 | 515 | 665 | 665 | 690 | 715 | 715 | 715 | 855 | 855 | 855 | 855 | 910 | 1130 | 1130 | 910 | 1130 | |
| 21 | Approximate gross weight of drum | kg | 120 | 135 | 165 | 185 | 230 | 295 | 300 | 355 | 460 | 540 | 725 | 830 | 1025 | 1260 | 1535 | 1010 | 1290 |
| 22 | Minimum bending radius for laying | 12 x Overall Diameter of cable | |||||||||||||||||
| of cable | |||||||||||||||||||
| 23 | Recommended pulling force: | ||||||||||||||||||
| a) When conductor pulled by pulling | |||||||||||||||||||
| eye | N | 30 x Total Conductor Area in mm2 | |||||||||||||||||
| b) When cable pulled with stocking | N | 5 x D2 where D is the Overall Diameter of cable in mm2 | |||||||||||||||||
| STRANDED CONDUCTOR IS ALSO PERMISSIBLE IN THESE SIZES | |||||||||||||||||||