1100
Volts Twin Core Armoured Cables |
|
(Aluminium
Conductor) Type 'AYWY' & "AYFY" to IS:1554(I) - 1988 |
|
Sl. |
|
|
Normal Cross-Sectional
Area of Conductor in mm2 |
|
|
|
|
|
|
|
|
|
|
|
No. |
Description |
Unit |
1.5 |
2.5 |
4 |
6 |
10 |
16 |
25 |
35 |
50 |
70 |
95 |
120 |
150 |
185 |
240 |
300 |
400 |
|
|
Constructional
Details |
|
|
|
|
|
Conductor (Solid) |
|
|
|
|
1 |
Minimum number of
wires |
nos. |
1 |
1 |
1 |
1 |
1 |
6 |
6 |
6 |
6 |
12 |
15 |
15 |
15 |
30 |
30 |
30 |
53 |
|
2 |
Shape |
|
|
|
Circular Solid |
|
|
compacted |
|
|
|
|
|
|
Shaped |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Conductor (Stranded) |
|
|
|
|
|
|
|
Minimum number of
wires |
nos. |
3 |
3 |
3 |
3 |
7 |
6 |
6 |
6 |
6 |
12 |
15 |
15 |
15 |
30 |
30 |
30 |
53 |
|
|
Shape |
|
|
|
Circular Stranded |
|
|
Compacted |
|
|
|
|
|
|
Shaped |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Insulation |
|
|
|
|
|
|
3 |
Type |
|
|
|
|
|
|
|
|
|
|
|
PVC Compound Type A to IS:5831 |
|
|
|
|
|
|
|
4 |
Nominal thickness |
mm |
0.8 |
0.9 |
1.0 |
1.0 |
1.0 |
1.0 |
1.2 |
1.2 |
1.4 |
1.4 |
1.6 |
1.6 |
1.8 |
2.0 |
2.2 |
2.4 |
2.6 |
|
|
5 |
Colour Scheme for
identification |
|
|
|
|
Red & Black |
|
|
|
|
6 |
Dia over laid up core |
|
|
|
9.50 |
10.70 |
12.50 |
14.60 |
13.55 |
15.03 |
17.78 |
19.91 |
23.18 |
25.13 |
28.40 |
31.33 |
35.14 |
39.12 |
44.15 |
|
|
7 |
Dia over inner sheath |
|
|
|
11.50 |
12.70 |
14.50 |
15.60 |
14.55 |
16.03 |
18.78 |
21.11 |
24.38 |
26.53 |
29.80 |
32.73 |
37.14 |
41.12 |
46.15 |
|
|
8 |
Dia over Armoured (Strip) |
|
|
|
|
|
|
17.20 |
16.15 |
17.63 |
20.38 |
22.71 |
25.98 |
28.13 |
31.40 |
34.33 |
38.74 |
42.72 |
47.75 |
|
|
9 |
Dia over Armoured (Wire) |
|
|
|
14.30 |
15.50 |
17.30 |
18.80 |
17.75 |
19.23 |
21.98 |
24.31 |
27.58 |
29.73 |
33.00 |
35.93 |
40.34 |
44.32 |
49.35 |
|
|
|
Inner Sheath |
|
|
|
|
|
|
|
10 |
Type |
|
|
|
Extruded |
|
|
|
|
|
|
|
|
|
Wrapped |
|
|
|
|
|
|
11 |
Material |
|
|
|
Unvulcanised Rubber |
|
|
|
|
|
|
|
|
|
PVC Taps |
|
|
|
|
|
|
12 |
Minimum Thickness |
mm |
0.3 |
0.3 |
0.3 |
0.3 |
0.3 |
0.3 |
0.3 |
0.3 |
0.3 |
0.3 |
0.4 |
0.4 |
0.4 |
0.5 |
0.5 |
0.6 |
0.7 |
|
|
|
Armouring |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
13 |
Type & Material |
|
|
|
Single Layer of Round |
|
|
|
|
Single
Layer of Flat Galvanised Steel Strip |
|
|
|
|
|
|
|
|
|
Galvanised Steel Wires |
|
|
|
|
|
|
|
14 |
Nominal Diamtr of wire
/thickness of strip |
mm |
1.4 |
1.4 |
1.4 |
1.4 |
1.4 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
|
|
|
Outer Sheath |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
15 |
Type |
|
|
|
|
|
|
|
|
|
|
|
PVC Compound Type ST 1 to IS:5831 |
|
|
|
|
|
|
|
|
16 |
Colour |
|
|
|
|
|
|
|
|
|
|
|
Black |
|
|
|
|
|
|
|
|
17 |
Minimum Thickness |
mm |
1.24 |
1.24 |
1.24 |
1.24 |
1.24 |
1.40 |
1.40 |
1.40 |
1.40 |
1.56 |
1.56 |
1.56 |
1.72 |
1.72 |
2.04 |
2.20 |
2.36 |
|
|
|
Appr overall diameter of cable
(Strip) |
mm |
|
|
|
|
|
19.90 |
18.85 |
20.33 |
23.08 |
25.41 |
28.98 |
31.13 |
34.40 |
37.33 |
41.74 |
46.04 |
51.07 |
|
|
Appr overall diameter of cable (Wire) |
mm |
|
|
17.00 |
18.20 |
20.00 |
21.50 |
20.45 |
21.93 |
24.68 |
27.31 |
30.58 |
32.73 |
36.00 |
38.93 |
42.60 |
47.64 |
52.67 |
|
|
ELECTRICAL CHARACTERISTICS |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
19 |
Resistance
of conductor per |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1000m length of completed cable |
|
|
|
|
|
|
a) Maximum d.c.
resistance at 20 Deg C |
ohm |
18.1 |
12.1 |
7.41 |
4.61 |
3.08 |
1.91 |
1.20 |
0.868 |
0.641 |
0.443 |
0.320 |
0.253 |
0.206 |
0.164 |
0.125 |
0.1 |
0.0778 |
|
|
b) a.c. resistance at 70 Deg. C |
ohm |
21.72 |
14.52 |
8.89 |
5.53 |
3.70 |
2.29 |
1.44 |
1.042 |
0.77 |
0.532 |
0.385 |
0.304 |
0.248 |
0.198 |
0.152 |
0.122 |
0.0962 |
|
20 |
Continuous current rating (a.c.)
of |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
cables under standard conditions |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
i) When laid direct
in ground |
amps |
18 |
25 |
32 |
40 |
55 |
70 |
90 |
110 |
135 |
160 |
190 |
210 |
240 |
275 |
320 |
355 |
385 |
|
|
ii) When laid in
ducts |
amps |
16 |
21 |
27 |
34 |
45 |
58 |
76 |
92 |
115 |
140 |
170 |
190 |
210 |
240 |
275 |
305 |
345 |
|
|
iii)When laid in air |
amps |
16 |
21 |
27 |
35 |
47 |
59 |
78 |
99 |
125 |
150 |
185 |
210 |
240 |
275 |
325 |
365 |
420 |
|
21 |
Reactance per 1000m
length of cable |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
at 50 Hz |
ohm |
0.092 |
0.087 |
0.081 |
0.073 |
0.064 |
0.055 |
0.054 |
0.05 |
0.05 |
0.046 |
0.043 |
0.042 |
0.042 |
0.042 |
0.041 |
0.040 |
0.040 |
|
22 |
Capacitance per 1000 m length
of cable |
Micro |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
farad |
0.31 |
0.34 |
0.38 |
0.43 |
0.52 |
0.63 |
0.67 |
0.75 |
0.76 |
0.88 |
0.89 |
0.98 |
0.98 |
0.98 |
1.03 |
1.04 |
1.08 |
|
|
1.92 |
23 |
Minimum volume
resistivity of PVC Insu |
ohm-cm |
|
|
|
|
|
|
|
|
|
|
1 X 10 13 AT 27 Deg C and 1 x 10 10 at 70 Deg C |
|
|
|
|
|
|
|
24 |
Maximum permissible
shortcircuit |
kilo |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
current for duration of one second |
amps |
0.114 |
0.190 |
0.304 |
0.456 |
0.760 |
1.216 |
1.900 |
2.660 |
3.800 |
5.320 |
7.220 |
9.120 |
11.400 |
14.060 |
18.240 |
22.800 |
30.400 |
|
25 |
Voltage drop per 1000m length
of |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
cable (assuming cable used on
single |
|
|
|
|
|
|
phase a.c. systems) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
a) When laid direct
in ground |
volts |
782 |
726 |
570 |
442 |
408 |
320 |
260 |
228 |
208 |
170 |
148 |
128 |
120 |
112 |
100 |
92 |
80 |
|
|
b) When laid in ducts |
volts |
696 |
610 |
480 |
376 |
334 |
266 |
218 |
192 |
178 |
150 |
132 |
116 |
106 |
98 |
86 |
78 |
72 |
|
|
c) When laid in air |
volts |
696 |
610 |
480 |
388 |
348 |
270 |
224 |
206 |
192 |
162 |
144 |
128 |
120 |
112 |
102 |
94 |
88 |
|
|
GENERAL : |
|
|
|
|
26 |
Approximate net weight per |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1000m length of finished cable
(Strip) |
kg |
|
|
|
|
|
603 |
649 |
756 |
945 |
1019 |
1414 |
1644 |
1947 |
2299 |
2870 |
3345 |
4179 |
|
|
Approximate net weight per |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1000m length of finished cable (Wire) |
kg |
|
|
516 |
579 |
678 |
809 |
844 |
969 |
1186 |
1394 |
1717 |
1970 |
2310 |
2694 |
3344 |
3933 |
4731 |
|
27 |
Standard length of
cable (Subject to a |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
manufacturing tolerance +/-5%) |
m |
|
|
|
|
|
|
|
|
|
|
500 |
|
|
|
|
250 |
250 |
|
28 |
Drum Dimensions- |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
a) Approximate
overall height |
mm |
840 |
940 |
940 |
1040 |
1040 |
1140 |
1140 |
1140 |
1250 |
1250 |
1450 |
1450 |
1650 |
1650 |
1850 |
1550 |
1650 |
|
|
b) Approximate outer
width |
mm |
665 |
690 |
690 |
715 |
715 |
715 |
715 |
715 |
855 |
855 |
855 |
855 |
1130 |
1130 |
1180 |
910 |
1130 |
|
29 |
Approximate gross
weight of drum |
kg |
265 |
310 |
355 |
400 |
455 |
400 |
455 |
490 |
615 |
735 |
935 |
1060 |
1345 |
1570 |
2020 |
1105 |
1475 |
|
30 |
Minimum bending
radius for laying of CBL |
|
|
|
|
|
|
|
|
|
|
|
12
x Overall Diameter of
Cable |
|
|
|
|
|
|
|
31 |
Recommended pulling
force: |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
a) When conductor
pulled by pulling eye |
N |
|
|
|
|
|
|
|
|
|
|
30 x Total Conductor Area in mm2 |
|
|
|
|
|
|
|
|
b) When cable pulled with stocking |
N |
|
|
|
|
|
|
|
|
|
|
9 x D2 where D is
the Overall Diameter of cable in mm |
|
|
|
|
|
|
|
|
|
|
STRANDED CONDUCTOR IS ALSO PERMISSIBLE IN THESE SIZES |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|