1100
Volts Three Core Unarmoured Cables |
|
(Aluminium
Conductor) Type 'AYY' to IS:1554(I) -
1988 |
|
Sl. |
|
|
Normal Cross-Sectional
Area of Conductor in mm2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
No. |
Description |
Unit |
1.5 |
2.5 |
4 |
6 |
10 |
16 |
25 |
35 |
50 |
70 |
95 |
120 |
150 |
185 |
240 |
300 |
400 |
500 |
630 |
|
|
Constructional
Details |
|
|
|
|
|
Conductor (Solid) |
|
|
|
|
1 |
Minimum number of
wires |
nos. |
1 |
1 |
1 |
1 |
1 |
6 |
6 |
6 |
6 |
12 |
15 |
15 |
15 |
30 |
30 |
30 |
53 |
53 |
53 |
|
2 |
Shape |
|
|
|
Circular Solid |
|
|
compaced |
|
|
|
|
|
|
Shaped |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Conductor (Stranded) |
|
|
|
|
|
Minimum number of
wires |
nos. |
3 |
3 |
3 |
3 |
7 |
6 |
6 |
6 |
6 |
12 |
15 |
15 |
15 |
30 |
30 |
30 |
53 |
53 |
53 |
|
|
Shape |
|
|
|
Circular Stranded |
|
|
compaced |
|
|
|
|
|
|
Shaped |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Insulation |
|
|
|
|
|
|
|
3 |
Type |
|
|
|
|
|
|
|
|
|
|
|
PVC Compound Type A to IS:5831 |
|
|
|
|
|
|
|
|
|
4 |
Nominal thickness |
mm |
0.8 |
0.9 |
1.0 |
1.0 |
1.0 |
1.0 |
1.2 |
1.2 |
1.4 |
1.4 |
1.6 |
1.6 |
1.8 |
2.0 |
2.2 |
2.4 |
2.6 |
3.0 |
3.4 |
|
5 |
Colour Scheme for
identification |
|
|
|
|
|
|
|
|
|
|
|
Red, Yellow, Blue |
|
|
|
|
|
|
|
|
|
6 |
Dai over laid up core |
|
|
|
10.16 |
11.68 |
12.51 |
13.33 |
16.34 |
18.31 |
21.65 |
24.44 |
28.27 |
30.86 |
34.50 |
38.27 |
43.20 |
47.99 |
54.61 |
|
|
|
7 |
Dia over inner sheath |
|
|
|
11.16 |
12.68 |
13.51 |
14.33 |
17.34 |
19.31 |
22.65 |
25.64 |
29.47 |
32.26 |
35.90 |
39.67 |
45.20 |
49.99 |
56.61 |
|
|
|
|
Inner Sheath &
Outer Sheath |
|
|
|
|
|
|
|
|
(Applied in one operation) |
|
|
|
|
|
|
|
8 |
Type |
|
|
|
|
|
|
|
|
|
|
|
PVC Compound Type ST 1 to IS:5831 |
|
|
|
|
|
|
|
|
|
9 |
Colour |
|
|
|
|
|
|
|
|
|
|
|
Black |
|
|
|
|
|
|
|
|
|
10 |
Minimum thickness of inner sheath |
mm |
0.30 |
0.30 |
0.30 |
0.30 |
0.30 |
0.30 |
0.30 |
0.30 |
0.30 |
0.40 |
0.40 |
0.40 |
0.50 |
0.50 |
0.60 |
0.60 |
0.70 |
0.70 |
0.70 |
|
11 |
Nominal thickness of outer sheath |
mm |
1.80 |
1.80 |
1.80 |
1.80 |
1.80 |
1.80 |
2.00 |
2.00 |
2.00 |
2.20 |
2.20 |
2.20 |
2.40 |
2.60 |
2.80 |
3.00 |
3.40 |
3.60 |
4.00 |
|
|
Approximate overall diameter of cable |
mm |
|
|
14.86 |
16.38 |
17.21 |
18.13 |
21.54 |
23.51 |
26.85 |
30.34 |
34.07 |
36.86 |
40.90 |
45.07 |
51.00 |
56.19 |
63.61 |
|
|
|
|
ELECTRICAL CHARACTERISTICS |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
13 |
Resistance
of conductor per |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1000m length of completed cable |
|
|
|
|
|
|
|
a) Maximum d.c.
resistance at 20 Deg C |
ohm |
18.1 |
12.1 |
7.41 |
4.61 |
3.08 |
1.91 |
1.20 |
0.868 |
0.641 |
0.443 |
0.320 |
0.253 |
0.206 |
0.164 |
0.125 |
0.1 |
0.0778 |
0.0605 |
0.0469 |
|
|
b) a.c. resistance at 70 Deg. C |
ohm |
21.72 |
14.52 |
8.89 |
5.53 |
3.70 |
2.29 |
1.44 |
1.042 |
0.77 |
0.532 |
0.385 |
0.304 |
0.248 |
0.198 |
0.152 |
0.122 |
0.0962 |
0.0762 |
0.0608 |
|
14 |
Continuous current rating (a.c.)
of |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
cables under standard conditions |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
i) When laid direct
in ground |
amps |
16 |
21 |
28 |
35 |
46 |
60 |
76 |
92 |
110 |
135 |
165 |
185 |
210 |
235 |
275 |
305 |
335 |
360 |
400 |
|
|
ii) When laid in
ducts |
amps |
14 |
18 |
23 |
30 |
39 |
50 |
63 |
77 |
95 |
115 |
140 |
155 |
175 |
200 |
235 |
260 |
290 |
305 |
340 |
|
|
iii)When laid in air |
amps |
13 |
18 |
23 |
30 |
40 |
51 |
70 |
86 |
105 |
130 |
155 |
180 |
205 |
240 |
280 |
315 |
375 |
410 |
470 |
|
15 |
Reactance per 1000m
length of cable |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
at 50 Hz |
ohm |
0.092 |
0.087 |
0.081 |
0.073 |
0.064 |
0.055 |
0.054 |
0.05 |
0.05 |
0.046 |
0.043 |
0.042 |
0.042 |
0.042 |
0.041 |
0.040 |
0.040 |
0.040 |
0.040 |
|
16 |
Capacitance between conductors
per |
Micro |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1000m length of cable |
farad |
0.113 |
0.120 |
0.130 |
0.140 |
0.160 |
0.180 |
0.180 |
0.200 |
0.200 |
0.210 |
0.220 |
0.230 |
0.230 |
0.230 |
0.230 |
0.230 |
0.240 |
0.240 |
0.240 |
|
|
17 |
Minimum volume
resistivity of PVC Insu |
Ohmcm |
|
|
|
|
|
|
|
|
|
|
1 X 10 13 AT 27 Deg C and 1 x 10 10 at 70 Deg C |
|
|
|
|
|
|
|
|
|
18 |
Maximum permissible
shortcircuit |
kilo |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
current for duration of one second |
amps |
0.114 |
0.190 |
0.304 |
0.456 |
0.760 |
1.216 |
1.900 |
2.660 |
3.800 |
5.320 |
7.220 |
9.120 |
11.400 |
14.060 |
18.240 |
22.800 |
30.400 |
38.000 |
47.880 |
|
19 |
Voltage drop per
1000m length of |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
cable (assuming three phase a.c. systems) |
|
|
|
|
|
|
a) When laid direct in ground |
volts |
602 |
528 |
431 |
335 |
295 |
238 |
190 |
166 |
147 |
125 |
112 |
99 |
91 |
81 |
76 |
69 |
60 |
54 |
51 |
|
|
b) When laid in ducts |
volts |
527 |
453 |
354 |
287 |
250 |
198 |
157 |
139 |
127 |
106 |
95 |
83 |
76 |
69 |
65 |
59 |
52 |
45 |
43 |
|
|
c) When laid in air |
volts |
489 |
453 |
354 |
287 |
256 |
202 |
175 |
155 |
140 |
120 |
105 |
97 |
89 |
81 |
78 |
71 |
68 |
61 |
59 |
|
|
GENERAL : |
|
|
|
|
20 |
Approximate net weight per |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1000m length of finished cable |
kg |
|
|
252 |
308 |
352 |
396 |
567 |
685 |
880 |
1160 |
1488 |
1767 |
2164 |
2654 |
3426 |
4182 |
5288 |
|
|
|
21 |
Standard length of
cable (Subject to a |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
manufacturing tolerance +/-5%) |
m |
|
|
|
|
|
|
|
|
500 |
|
|
|
|
|
|
|
|
250 |
|
|
22 |
Drum Dimensions- |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
a) Approximate
overall height |
mm |
840 |
840 |
840 |
940 |
940 |
1040 |
1140 |
1250 |
1250 |
1450 |
1550 |
1650 |
1650 |
1850 |
2265 |
1650 |
1850 |
2050 |
2265 |
|
|
b) Approximate outer
width |
mm |
515 |
665 |
665 |
690 |
690 |
715 |
715 |
855 |
855 |
855 |
910 |
1130 |
1130 |
1180 |
1420 |
1130 |
1180 |
1240 |
1350 |
|
23 |
Approximate gross
weight of drum |
kg |
125 |
150 |
275 |
215 |
255 |
325 |
395 |
485 |
580 |
780 |
1005 |
1230 |
1435 |
1830 |
2640 |
1420 |
1865 |
2340 |
3050 |
|
24 |
Minimum bending
radius for laying of CBL |
|
|
|
|
|
|
|
|
|
|
|
12
x Overall Diameter of
Cable |
|
|
|
|
|
|
|
|
|
25 |
Recommended pulling
force: |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
a) When conductor
pulled by pulling eye |
N |
|
|
|
|
|
|
|
|
|
|
30 x Total Conductor Area in mm2 |
|
|
|
|
|
|
|
|
|
|
b) When cable pulled with stocking |
N |
|
|
|
|
|
|
|
|
|
|
5 x D2 where D is
the Overall Diameter of cable in mm |
|
|
|
|
|
|
|
|
|
|
|
|
STRANDED CONDUCTOR IS ALSO PERMISSIBLE IN THESE SIZES |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|