1100
Volts Three & Half Core Armoured Cables |
|
|
|
(Aluminium
Conductor) Type 'AYFY' to IS:1554(I) -
1988 |
|
|
|
|
|
|
|
Normal Cross-Sectional
Area of Conductor in mm2 |
|
|
|
|
|
|
|
|
|
|
Main |
25 |
35 |
50 |
70 |
95 |
120 |
150 |
185 |
240 |
300 |
400 |
500 |
630 |
|
No. |
Description |
Unit |
Neutral |
16 |
16 |
25 |
35 |
50 |
70 |
70 |
95 |
120 |
150 |
185 |
240 |
300 |
|
|
CONSTRUCTION DETAILS |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Conductor |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 |
Minimum number of
wires |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
a) Main conductor |
nos. |
|
6 |
6 |
6 |
12 |
15 |
15 |
15 |
30 |
30 |
30 |
53 |
53 |
53 |
|
|
b) Neutral Conductor |
nos. |
|
6 |
6 |
6 |
6 |
6 |
12 |
12 |
15 |
15 |
15 |
30 |
30 |
30 |
|
2 |
Shape |
|
|
|
|
|
|
a) Main conductor |
|
|
|
|
|
|
|
|
|
Shaped stranded |
|
|
|
|
|
|
|
b) Neutral Conductor |
|
|
Circulated |
|
|
|
|
|
|
Shaped Stranded |
|
|
|
|
|
|
|
|
|
Compacted |
|
|
|
|
|
|
|
|
|
|
|
|
|
Insulation |
|
|
|
|
|
3 |
Type |
|
|
|
|
|
|
|
|
|
PVC Compound Type A to IS:5831 |
|
|
|
|
|
|
4 |
Nominal thickness |
|
|
|
|
|
|
|
|
|
|
|
a) Main Core |
mm |
|
1.2 |
1.2 |
1.4 |
1.4 |
1.6 |
1.6 |
1.8 |
2.0 |
2.2 |
2.4 |
2.6 |
3.0 |
3.4 |
|
|
|
|
|
b) Neutral Core |
mm |
|
1.0 |
1.0 |
1.2 |
1.2 |
1.4 |
1.4 |
1.4 |
1.6 |
1.6 |
1.8 |
2.0 |
2.2 |
2.4 |
|
|
|
|
5 |
Colour Scheme for
identification |
|
|
|
|
|
Red, Yellow, Blue FOR Main Cores and Black for Neutral Core |
|
|
|
|
|
|
Inner Sheath |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
6 |
Type |
|
|
|
|
|
|
|
|
|
Extruded |
|
|
|
|
|
|
|
|
7 |
Material |
|
|
|
|
|
|
|
|
|
PVC Tapes |
|
|
|
|
|
|
|
|
8 |
Minimum Thickness |
|
|
0.3 |
0.3 |
0.3 |
0.4 |
0.4 |
0.5 |
0.5 |
0.5 |
0.6 |
0.6 |
0.7 |
0.7 |
0.7 |
|
|
|
|
Armouring |
|
|
|
|
|
|
|
|
|
9 |
Type & Material |
|
|
|
|
|
|
|
|
|
Single Layer of Flat Galvanised Steel Strips |
|
|
|
|
|
|
|
|
10 |
Nominal Thickness of
strips |
|
|
|
|
|
|
|
|
|
0.8 |
|
|
|
|
|
|
|
|
|
Outer Sheath |
|
|
|
|
|
|
|
|
|
11 |
Type |
|
|
|
|
|
|
|
|
|
PVC Compound Type ST 1 to IS:5831 |
|
|
|
|
|
|
|
|
12 |
Colour |
|
|
|
|
|
Black |
|
|
|
|
|
13 |
Minimum Thickness |
mm |
|
1.4 |
1.4 |
1.56 |
1.56 |
1.56 |
1.72 |
1.88 |
2.04 |
2.2 |
2.36 |
2.68 |
2.84 |
3.0 |
|
14 |
Dia over
Laidup core |
mm |
|
16.93 |
18.94 |
22.74 |
27.28 |
31.57 |
34.51 |
38.58 |
42.80 |
48.33 |
53.71 |
59.21 |
|
|
|
15 |
Dia over Inner Sheath |
mm |
|
17.93 |
19.94 |
23.74 |
28.48 |
32.77 |
35.91 |
39.98 |
44.40 |
49.93 |
55.71 |
61.21 |
|
|
|
16 |
Dia over Armoured (Strip) |
mm |
|
19.53 |
21.54 |
25.34 |
30.08 |
34.37 |
37.51 |
41.58 |
46.0 |
51.53 |
57.31 |
62.81 |
|
|
|
|
Dia over Armoured (Wire) |
mm |
|
21.13 |
23.14 |
26.94 |
32.48 |
36.77 |
39.91 |
43.98 |
49.40 |
54.93 |
62.01 |
67.51 |
|
|
|
|
Approximate overall
diameter of cable (Strip) |
mm |
|
22.53 |
24.54 |
28.66 |
33.40 |
37.69 |
41.21 |
45.58 |
50.30 |
56.13 |
62.23 |
68.41 |
|
|
|
|
Approximate overall
diameter of cable (Wire) |
mm |
|
24.13 |
26.14 |
30.26 |
35.80 |
40.47 |
43.91 |
47.98 |
53.70 |
59.93 |
67.31 |
73.31 |
|
|
|
|
ELECTRICAL
CHARACTERISTICS |
|
|
|
|
|
18 |
Resistance of conductor per 1000m
length of completed cables |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
a) Maximum d.c. resistance at 20 Deg
C main conductor |
ohm |
|
1.200 |
0.868 |
0.641 |
0.443 |
0.320 |
0.253 |
0.206 |
0.164 |
0.125 |
0.100 |
0.0778 |
0.0605 |
0.469 |
|
|
b) Maximum d.c. resistance at 20 Deg.
C Neutral conductor |
ohm |
|
1.910 |
1.910 |
1.200 |
0.868 |
0.641 |
0.443 |
0.443 |
0.320 |
0.253 |
0.206 |
0.164 |
0.125 |
0.100 |
|
|
c) a.c. resistance at
70 Deg C for main cond |
ohm |
|
1.440 |
1.042 |
0.770 |
0.532 |
0.385 |
0.304 |
0.248 |
0.198 |
0.152 |
0.122 |
0.0962 |
0.0762 |
0.0608 |
|
19 |
Continuous current rating (a.c.) of
cables under stranded conditions |
|
|
|
|
|
|
i) When laid direct in ground |
amps |
|
76 |
92 |
110 |
135 |
165 |
185 |
210 |
235 |
275 |
305 |
335 |
360 |
400 |
|
|
ii) When laid in
ducts |
amps |
|
63 |
77 |
95 |
115 |
140 |
155 |
175 |
200 |
235 |
260 |
290 |
305 |
340 |
|
|
iii)When laid in air |
amps |
|
70 |
86 |
105 |
130 |
155 |
180 |
205 |
240 |
280 |
315 |
375 |
410 |
470 |
|
20 |
Reactance per 1000m
length of cable at 50 Hz |
|
|
0.054 |
0.050 |
0.050 |
0.046 |
0.043 |
0.042 |
0.042 |
0.042 |
0.041 |
0.040 |
0.040 |
0.040 |
0.040 |
|
21 |
Star Capacitance per 1000 m length of
cable |
Micro |
|
0.80 |
0.90 |
0.91 |
1.03 |
1.064 |
1.16 |
1.16 |
1.18 |
1.22 |
1.25 |
1.30 |
1.30 |
1.30 |
|
|
|
farad |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
22 |
Minimum volume
resistivity of Insulation |
Ohmcm |
|
|
|
|
|
|
|
|
1 X 10 13 AT 27 Deg C and 1 x 10 10 at 70 Deg C |
|
|
|
|
|
|
23 |
Maximum permissible
shortcircuit Current for duration of one second |
kilo amps |
|
1.900 |
2.660 |
3.800 |
5.320 |
7.220 |
9.120 |
11.400 |
14.060 |
18.240 |
22.800 |
30.400 |
38.00 |
47.880 |
|
24 |
Voltage drop per 1000m length of cable (assuming cbl 3 phase
a.c. systems) |
|
|
|
|
|
|
a) When laid direct in ground |
volts |
|
190 |
166 |
147 |
125 |
112 |
99 |
91 |
81 |
76 |
69 |
60 |
54 |
51 |
|
|
b) When laid in ducts |
volts |
|
157 |
139 |
127 |
106 |
95 |
83 |
76 |
69 |
65 |
59 |
52 |
45 |
43 |
|
|
c) When laid in air |
volts |
|
175 |
155 |
140 |
120 |
105 |
97 |
89 |
81 |
78 |
71 |
68 |
61 |
59 |
|
|
GENERAL : |
|
|
|
|
|
25 |
Approximate net
weight per 1000 m length of finished cable (Strip) |
kg |
|
924 |
1078 |
1403 |
1787 |
2225 |
2667 |
3137 |
3895 |
4675 |
5690 |
6963 |
|
|
|
|
Approximate net weight per 1000 m
length of finished cable (Wire) |
kg |
|
1165 |
1340 |
1710 |
2375 |
2958 |
3457 |
3975 |
5187 |
6285 |
6940 |
9699 |
|
|
|
26 |
Standard length of cable (Subject to
a manufacturing tolerance +/-5% |
|
|
|
|
|
|
500 |
|
|
|
|
|
|
250 |
|
|
|
|
27 |
Drum Dimensions- |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
a) Approximate
overall height |
mm |
|
1250 |
1250 |
1450 |
1550 |
1650 |
1650 |
1850 |
2265 |
2265 |
1850 |
2050 |
2265 |
2465 |
|
|
b) Approximate outer
width |
mm |
|
855 |
855 |
855 |
910 |
1130 |
1130 |
1180 |
1420 |
1420 |
1180 |
1240 |
1350 |
1450 |
|
28 |
Approximate gross
weight of drum |
kg |
|
650 |
725 |
985 |
1170 |
1475 |
1715 |
2085 |
2895 |
3360 |
1940 |
2475 |
3135 |
3345 |
|
29 |
Minimum bending
radius for laying of CBL |
|
|
|
|
|
|
|
|
|
12
x Overall Diameter of
Cable |
|
|
|
|
|
|
30 |
Recommended pulling
force: |
|
|
|
|
|
|
a) When conductor
pulled by pulling eye |
N |
|
|
|
|
|
|
|
|
30 x Total
Conductor Area in mm2 |
|
|
|
|
|
|
|
b) When cable pulled with stocking |
N |
|
|
|
|
|
|
9 x D2 where D is the Overall Diameter of cable in mm |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|